Dimensions Table
| Pump Model | Discharge | Suction | A | B | C | D | F (Sq.) | G (Sq.) | H | J | K | GG (Dia.) |
| VSABM-4B | 4 | 4 | 6.5 | 16.5 | 15.75 | 8.5 | 15 | 13.25 | 9 | 6.75 | 0.875 | - |
| VSABM-4E | 4 | 4 | 5.5 | 16.375 | 29.25 | 6.5 | 15.5 | - | 9.5 | 8.125 | 0.625 | 19.5 |
| VSABM-6H | 6 | 6 | 7 | 19.625 | 29.5 | 8 | 19.75 | - | 9.5 | 9.5 | 0.625 | 25.5 |
Notes:
1. All dimensions are in inches unless otherwise noted. Do not use for construction purposes unless certified
2. Suction and discharge flanges are 125# ASA standard.
3. VSABM-4B pumps are available with right hand rotation only, VSABM-4E and VSABM-6H pumps are available with right hand or left hand rotation. The right hand rotation discharge position '1R' is standard on all pumps unless otherwise specified.
Notes
1. All dimensions are in inches unless otherwise stated. Do not use for construction purposes unless certified.
2. The following equipment is furnished by federal pump corporation: pump, universal shafting, steady bearings (if required), grouting plate, motor pedestal and motor.
3. The following equipmentis furnished by others: foundation bolts, concrete base for pump, support members for steady bearings (if required).
4. Universal shafting is furnished in one, two, or three sections, depending on the floor-to-floor distance and the motor H.P. and R.P.M. One section shafting does not require a steady bearing, two section shafting requires one steady bearing, and three section shafting requires two steady bearings.
5. Contractor must furnish "D" and "P" dimensions, to permit proper sizing of shafting.
Unknown
| Motor Frame | AG Approx. |
| 182C | 14 |
| 184C | 14 |
| 213C | 17 |
| 215C | 17 |
| 254UC | 21 |
| 256UC | 21 |
| 284UC | 23 |
| 286UC | 23 |
| 324UC | 24 |
| 326UC | 24 |
| 364UC | 30 |
| 365UC | 30 |
Notes:
1. Sump pump should be Federal model VB-1-1/2-1/3-4 with single phase motor. Sump pump discharge should be piped up and back into the wet well. Provide independent power supply.
2. Equipment and fitting not shown as 'by F.P.C.' Are generally furnished by others.
3. For information on Federal type SBS Submers-a-bulb controls, see No. 263.
4. Proper lighting and ventilation of the dry well should be provided, plus convenient access and ladders in both wet and dry wells. Electrically operated dehumidifier is recommended for the dry well, with its drain piped to sump pit.
Notes:
1. All dimensions are in inches unless stated otherwise. Do not use for construction purposes unless certified.
2. The following equipment is furnished by Federal Pump Corporation: pump, universal shafting, steady bearings (if required), grouting plate, motor pedestal and motor.
3. The following equipment is furnished by others: foundation bolts, concrete base for pump, support members for the steady bearings (if required).
4. Universal shafting is furnished in one, two or three sections, depending on the floor-to-floor distance and the motor H.P, and R.P.M. One-section shafting does not require a steady bearing, two section shafting requires one steady bearing and three-section shafting requires two steady bearings.
5. Contractor must furnish 'D' and 'P' dimensions, to permit proper sizing of shafting.