Features

RECEIVING TANK: Heavy steel construction, mounted on steel legs, and fitted with thermometer and gauge glass.

MAKEUP WATER VALVE: All-bronze float actuated valve, flange mounted in tank head, permits entry of makeup water, when required, to replace system losses. Complete with strainer on makeup water connection.

PUMPS: Regenerative peripheral turbine vane type, vertically split, with removable covers and channel rings, ball bearings, stainless steel shaft, bronze impeller and mechanical shaft seals.

MOTORS: Drip-proof ball bearing type flexibly-coupled to pumps. Single phase motors 3/4 H.P. and smaller have built-in overload protection. Single phase motors 1 H.P. and larger and all three phase motors are furnished with magnetic starters in NEMA-1 wall-mounting enclosures.

UNITS: Unit is factory assembled on single steel base with pump suction piping complete, including strainer in each pump suction line. Simplex unit has one receiving tank, one makeup valve and one pump and motor. Duplex unit has one receiving tank, one makeup valve and two pumps and motors. Triplex and quadruplex units are also available.

OPERATION: Boiler feed pump(s) is controlled by a boiler water level controller mounted on the boiler. These controllers are usually furnished with integral low water cut-off and alarm switches. Boiler feed water is taken from the receiver, and if condensate has been lost in the system, it is automatically replaced by the makeup valve.

Highlights

Modifications List

NON-STANDARD TANK SIZES: Units can be furnished with tank capacities other than shown in the selection table. Diameters and lengths of receivers can be modified where required by space conditions. Return inlet height and location can be modified.

GALVANIZING OF RECEIVER: Hot-dip galvanized inside and outside.

SPECIAL RECEIVER COATINGS: Special interior and exterior coatings where job conditions require extra corrosion resistance.

INTERIOR TANK BAFFLES: Built into tank to prevent air or sludge from entering pump suction.

SPECIAL RECEIVER TAPPINGS: Special or additional tappings as required.

MANHOLE: Manhole and bolted cover for clean-out and inspection.

DRAIN VALVE: Tank drain connection can be fitted with bronze drain valve.

EXTERNAL FLOAT CHAMBER MAKEUP VALVE: Mounted on end of receiver with 3-valve by-pass piping to permit manual and automatic makeup water control. Has built-in strainer.

SOLENOID OPERATED MAKEUP VALVE: Furnished with reverse-acting float switch in receiver to actuate the solenoid valve. Requires electric service for operation and is furnished with makeup water strainer. Can be furnished with air gap and 3-valve by-pass, if required.

CORROSION INHIBITOR BAR: Magnesium anode bar in the receiver to inhibit electrolytic corrosion; with drip-hole to indicate when bar has been completely corroded and requires replacement.

FEED WATER HEATERS: Submerged perforated brass feed water heater pipe, operated by temperature sensor and regulating steam valve.

SPECIAL THERMOMETER: Standard column type can be replaced by special thermometers as specified.

NON-STANDARD MOTOR CONTROLS: "Hand-off-Automatic" selector switch, pilot light and control circuit transformer for motor starters; waterproof or explosion-proof enclosures for starters; combination magnetic starters and disconnect switches, plus combination magnetic starters and circuit breakers.

PRESSURE GAUGES: Pump discharge pressure gauges available.

NON-STANDARD MOTOR ENCLOSURES: Standard enclosures are drip-proof. Totally enclosed and explosion-proof enclosures are available.

TRANSFER SWITCHES: To alternate pump operation or transfer pump-boiler relationship in multiple-boiler installations.

CONTROL PANELS: Control components can be mounted on factory-wired wall-mounting or floor-mounting panel, in lieu of individual wall-mounting enclosures.

LARGER UNITS: For ratings in excess of 750 Boiler H.P. and discharge pressures in excess of 200 psig, up to a maximum of 400 psig, consult factory or nearest Federal Pump representative.

OVERFLOW LOOP: An overflow loop can be piped from the tank head, if required.

WATER LEVEL ALARMS: A high water alarm and/or low water alarm float switch can be furnished in the receiver with alarm station and/or pump cutout circuit.

GATE VALVES: A gate valve can be installed in each pump suction line, if required.



cad - bfu-bft-specifications_56a.gif

Dimensions Table

Unit NumberTank Cap. Gal.Tank Shell SizeABCDE*F*GHJDrain
BFT-2015-4 THRU BFT-20200-42618x24362630212831210.51
BFT-3015-4 THRU BFT-30200-43318x28402634212831310.51
BFT-5015-4 THRU BFT-50200-44518x36482642212831310.51
BFT-6015-4 THRU BFT-60200-46322x3648264223303331.250.51
BFT-8015-4 THRU BFT-100200-410024x4860265424343841.250.51
BFT-15015-4 THRU BFT-150200-415030x4860325432404441.50.751.25
BFT-20015-4 THRU BFT-200200-422030x72935087405155420.751.5
BFT-25015-4 THRU BFT-250200-425030x841055099405155420.751.5
BFT-30015-4 THRU BFT-300200-431536x72935087435761420.751.5
BFT-35015-4 THRU BFT-400200-439036x841055099435761420.751.5
BFT-50015-4 THRU BFT-600200-450042x841055499486367420.751.5
BFT-75015-4 THRV BFT-750200-475048x961175411151697362.512
NON-STD. TANK100048x1201415413551697362.512
*For units with tank sizes 150 gallons and smaller, add 5 inches to the E and F dimensions when the unit uses 5 and 6 series pumps.

Equivalents Table

1,000 sq. ft. E.D.R.=240,000 BTU per hr.
1,000 sq. ft. E.D.R.=247 lbs. Water Evap. per hr.
1,000 sq. ft. E.D.R.=1/2 gal. Water Evap. per min.
1 sq. ft. E.D.R.=240 BTU per hr. (Steam)
1 sq. ft. E.D.R.=150 BTU per hr. (Hot Water)
1 sq. ft. E.D.R.=1/4 lb. Water Evap. per hr.
1 Boiler HP.=33,475 BTU per hr.
1 Boiler HP.=34.5 lbs. Water Evap. Per hr. (at 212 degrees F)
1 Boiler HP.=.07 gal. Water Evap. per min.
1 Boiler HP.=140 sq. ft. E.D.R. (Steam)
1 Boiler HP.=222 sq. ft. E.D.R. (Hot Water)
1 lb. P.S.I.=2.31 ft. of Water
1 lb. P.S.I.=2.04 ins. of Mercury
1 lb. P.S.I.=.068 Atmosphere
1 ft. of Water=.433 lbs. P.S.I.
1 ft. of Water=.882 ins. of Mercury
1 ft. of Water=.029 Atmosphere

 

SIZING DATA

PUMP CAPACITY: Multiply the developed boiler H.P. by .07 to determine the evaporation rate of the boiler (expressed in gallons per minute). Next, multiply this evaporation rate by 3 to determine the capacity of the feed pump (in G.P.M). This factor of 3 allows the pump to cycle at reasonable intervals. If one boiler is being fed, a simplex unit may be used, but a duplex unit (with each pump sized to independently feed the boiler has the advantage of providing an emergency standby pump or alternating the pumps for even wear. If two boilers are being fed, use duplex unit and size one pump for each boiler (specify 4-pole double throw transfer switch to cross pump-boiler assignment) or use triplex unit with each pump sized to feed one of the boilers (specify transfer switch to use one pump for standby service).
PUMP DISCHARGE PRESSURE:
Discharge pressures in the Engineering Selection Table are pressures at the pump. To compute, add boiler working pressure plus static head (from pump center line to boiler connection center line) plus discharge line friction loss (including pipe, fittings, valves, etc). Convert all factors to P.S.I. before adding. Static head plus friction loss plus a small residual pressure can be estimated at 5 P.S.I. in most cases.
RECEIVER SIZE: Allow approximately one gallon of receiver, capacity for each H.P. of boiler(s) being served. (Example: If two (2) 250 H.P. boilers are being fed by a duplex unit, receiver should have 500 gallon capacity.)

cad - bfu-bft-engineering_54a.gif


Selection Table

Unit No.Boiler H.P.Pump Disch. Press P.S.I.G.Boiler Evap. G.P.M.FactorPump Capacity G.P.MMotor H.P. 1750 RPMReceiving Tank Capacity Gal.Pump Disch. Size
BFT-2015-420151.42.530.25261.25
BFT-2050-420501.42.530.5261.25
BFT-2075-420751.42.530.75261.25
BFT-20100-4201001.42.530.75261.25
BFT-20125-4201251.42.531261.25
BFT-20150-4201501.42.531261.25
BFT-20200-4202001.42.531.5261.25
BFT-3015-430152.12.550.25331.25
BFT-3050-430502.12.550.5331.25
BFT-3075-430752.12.551331.25
BFT-30100-4301002.12.551331.25
BFT-30125-4301252.12.551.5331.25
BFT-30150-4301502.12.552331.25
BFT-30200-4302002.12.552331.25
BFT-5015-450153.5270.25451.25
BFT-5050-450503.5270.5451.25
BFT-5075-450753.5271451.25
BFT-50100-4501003.5271451.25
BFT-50125-4501253.5272451.25
BFT-50150-4501503.5271.5451.25
BFT-50200-4502003.5272451.25
BFT-6015-460154.2290.25631.25
BFT-6050-460504.2291631.25
BFT-6075-460754.2290.75631.25
BFT-60100-4601004.2291.5631.25
BFT-60125-4601254.2292631.25
BFT-60150-4601504.2293631.25
BFT-60200-4602004.2295631.25
BFT-8015-480155.52110.331001.25
BFT-8050-480505.521111001.25
BFT-8075-480755.521111001.25
BFT-80100-4801005.521121001.25
BFT-80125-4801255.521121001.25
BFT-80150-4801505.521131001.25
BFT-80200-4802005.521151001.25
BFT-10015-4100156.92140.331001.25
BFT-10050-4100506.92141.51001.25
BFT-10075-4100756.92141.51001.25
BFT-100100-41001006.921431001.25
BFT-100125-41001256.921431001.25
BFT-100150-41001506.921451001.25
BFT-100200-41002006.92147.51001.25
BFT-15015-41501510.42200.51501.25
BFT-15050-41505010.42201.51501.25
BFT-15075-41507510.422021501.25
BFT-150100-415010010.422031501.25
BFT-150125-415012510.422051501.25
BFT-150150-415015010.422051501.25
BFT-150200-415020010.42207.51502
BFT-20015-42001513.822812201.25
BFT-20050-42005013.822832202
BFT-20075-42007513.822852202
BFT-200100-420010013.822832201.25
BFT-200125-420012513.822852201.25
BFT-200150-420015013.82287.52202
BFT-200200-420020013.8228102202
BFT-25015-42501517.32351.52502
BFT-25050-42505017.323532502
BFT-25075-42507517.323552502
BFT-250100-425010017.32357.52502
BFT-250125-425012517.32357.52502
BFT-250150-425015017.32357.52502
BFT-250200-425020017.3235152502
BFT-30015-43001520.71.753623152
BFT-30050-43005020.71.753633152
BFT-30075-43007520.71.753653152
BFT-300100-430010020.71.75367.53152
BFT-300125-430012520.71.75367.53152
BFT-300150-430015020.71.75367.53152
BFT-300200-430020020.71.7536153152
BFT-35015-43501524.21.754233902
BFT-35050-43505024.21.754233902
BFT-35075-43507524.21.754253902
BFT-350100-435010024.21.75427.53902
BFT-350125-435012524.21.7542103902
BFT-350150-435015024.21.7542103902
BFT-350200-435020024.21.7542153902
BFT-40015-44001527.61.754833902
BFT-40050-44005027.61.754853902
BFT-40075-44007527.61.754853902
BFT-400100-440010027.61.75487.53902
BFT-400125-440012527.61.7548103902
BFT-400150-440015027.61.7548103902
BFT-400200-440020027.61.7548153902
BFT-50015-45001534.51.756035002
BFT-50050-45005034.51.756055002
BFT-50075-45007534.51.756055002
BFT-500100-450010034.51.7560105002
BFT-500125-450012534.51.7560155002
BFT-500150-450015034.51.7560155002
BFT-500200-450020034.51.7560205002
BFT-60015-46001541.51.757335002
BFT-60050-46005041.51.757355002
BFT-60075-46007541.51.7573105002
BFT-600100-460010041.51.7573105002
BFT-600125-460012541.51.7573155002
BFT-600150-460015041.51.7573205002
BFT-600200-460020041.51.7573255002
BFT-75015-47501551.81.759137502
BFT-75050-47505051.81.759157502
BFT-75075-47507551.81.7591107502
BFT-750100-475010051.81.7591107502
BFT-750125-475012551.81.7591207502
BFT-750150-475015051.81.7591207502
BFT-750200-475020051.81.7591307502
Explantion of unit numbers: Example BFT-200125-4; BFT is the type of unit (packaged boiler feed unit with turbine type boiler feed pumps); -200 is the rated horsepower of the boiler being fed; 125 is the pump discharge pressure (in psig); -4 is the speed of the motor (-4 indicates 4-pole 1750 R.P.M.)
Higher pump discharge pressures: BFT Units may be furnished with pump discharge pressures of up to 400 psig.


SUGGESTED SPECIFICATIONS FOR ARCHITECTS AND ENGINEERS:

Furnish and install where shown on plans, Type BFT Simplex (or Duplex; or Triplex, etc.) Boiler Feed Unit, as manufactured by Federal Pump Corporation, Unit No. BFT ________, having a capacity of_________ Boiler H.P. (per pump), with pump capacity of________ G.P.M. (per pump), at a discharge pressure of _______ P.S.I.G. Unit to be completely assembled at the factory, comprising tank, accessories, pump(s) and motor(s), on steel bed plate, with suction piping between tank and pump(s) complete, including strainer in (each) pump suction line.Pump to be bronze fitted, peripheral regenerative turbine type, with double outboard ball bearings, mechanical shaft seal and stainless steel shaft and driven through flexible coupling by ______ H.P., ______R.P.M., _______Phase, _______cycles, _________ volts, drip-proof, ball bearing motor.

Tank to be elevated, horizontal, cylindrical, heavy, welded steel construction, with special high temperature corrosion resistant interior coating, equipped with reinforced threaded pipe connections for return inlet, air vent, drain, gauge glass and thermometer. The cold water makeup valve assembly shall be flanged to one head of the tank and shall be of all bronze construction, with interior copper float and inlet strainer.

Tank to be of ______ gallon capacity.For single phase motors, 3/4 H.P. or less, specify a built-in thermal overload device for each motor. For single phase motors, 1 H.P. or larger, and all three phase motors specify a magnetic line voltage starter for each motor.Furnish (for each boiler) one (1) boiler water level controller for automatic operation of pump(s), and maintenance of proper boiler water level. This controller to be equipped with low water cut-off and alarm switches, and alarm bell.