Features

RECEIVING TANK: Heavy steel construction, mounted on steel legs, and fitted with thermometer and gauge glass.

MAKEUP WATER VALVE: All-bronze float actuated valve, flange mounted in tank head, permits entry of makeup water when required, to replace system losses. Complete with strainer on make-up water connection.

PUMP(S): Close-coupled, bronze-fitted, centrifugal design, with leakless mechanical shaft seal.

MOTOR(S): Drip-proof ball bearing type close-coupled to pump(s). Single phase motors in fractional H.P. frame sizes have built-in thermal overload protection. Single phase motors in integral H.P. frame sizes, and all 3 phase motors, are furnished with magnetic starters in NEMA 1 general purpose wall-mounting enclosures. Units are available with 1750 R.P.M. or 3450 R.P.M. motors (see Engineering Selection Table).

UNITS: Unit is factory assembled on single steel base with pump suction piping complete. Simplex unit has one receiving tank, one makeup valve and one pump and motor. Duplex unit has one receiving tank, one makeup valve, and two pumps and motors. Triplex unit has one receiving tank, one makeup valve and three pumps and motors. Quadruplex unit has one receiving tank, one makeup valve and four pumps and motors.

OPERATION: Boiler feed pump(s) is controlled by a boiler water level controller mounted on the boiler. These controllers are usually furnished with integral low water cut-off and alarm switches. Boiler feed water is taken from the receiver, and if condensate has been lost in the system, it is automatically replaced by the makeup valve.

Highlights

Modifications List

NON-STANDARD TANK SIZES: Units can be furnished with tank capacities other than shown in the selection table. Diameters and lengths of receivers can be modified where required by space conditions. Return inlet height and location can be modified.

GALVANIZING OF RECEIVER: Hot-dip galvanized inside and outside.

SPECIAL RECEIVER COATINGS: Special interior and exterior coatings where job conditions require extra corrosion resistance.

INTERIOR TANK BAFFLES: Built into tank to prevent air or sludge from entering pump suction.

SPECIAL RECEIVER TAPPINGS: Special or additional tappings as required.

MANHOLE: Manhole and bolted cover for clean-out and inspection.

DRAIN VALVE: Tank drain connection can be fitted with bronze drain valve.

EXTERNAL FLOAT CHAMBER MAKEUP VALVE: Mounted on end of receiver with 3-valve by-pass piping to permit manual and automatic makeup water control. Has built-in strainer.

SOLENOID OPERATED MAKEUP VALVE: Furnished with reverse-acting float switch in receiver to actuate the solenoid valve. Requires electric service for operation and is furnished with makeup water strainer. Can be furnished with or without air gap.

CORROSION INHIBITOR BAR: Magnesium anode bar in the receiver to inhibit electrolytic corrosion; with drip-hole to indicate when bar has been completely corroded and requires replacement.

FEED WATER HEATERS: Perforated brass steam injection pipe operated by temperature regulating valve with sensor.

SPECIAL THERMOMETER: Standard column type can be replaced by special thermometers as specified.

PRESSURE GAUGES: Pressure gauge available for each pump discharge.

NON-STANDARD MOTOR ENCLOSURES: Standard enclosures are drip-proof. Totally enclosed and explosion-proof enclosures are available.

TRANSFER SWITCHES: To alternate pump operation or transfer pump-boiler relationship in multiple-boiler installations.

CONTROL PANELS: Control components can be mounted on factory-wired wall-mounting or floor-mounting panel, in lieu of individual wall-mounting enclosures.

NON-STANDARD MOTOR CONTROLS: "Hand-off-Automatic" selector switch, pilot light and control circuit transformer for motor starters; waterproof or explosion-proof enclosures for starters; combination magnetic starters and disconnect switches, plus combination magnetic starters and circuit breakers.

FLEXIBLY-COUPLED PUMPS: Can be substituted for the standard close-coupled pumps.

LARGER UNITS: For ratings in excess of 1000 Boiler H.P. and discharge pressures up to 125 psi, consult Factory or nearest Federal Pump representative.

STRAINERS: In pump suction lines or fitted to the return inlet connection of receiver.

CONDENSATION RETURN UNITS: BFC Units can be furnished as condensation return units by substituting a float switch in the receiver to operate each pump and removing the make-up water valve.

SUCTION GATE VALVE: Can be added in each pump suction line to isolate pump from tank.



cad - bfu-bfc-specifications_45a.gif
cad - bfu-bfc-specifications_45b.gif

Dimensions Table

Unit NumberFigureTank Cap. Gal.Tank Shell SizeACGHJDrain
BFC-1510 THRU 158012618x243632210.51
BFC-3010 THRU 308013318x284036310.51
BFC-5010 THRU 508014518x364844310.51
BFC-7510 THRU 7580110024x48615741.250.51
BFC-10010 THRU 10080110024x48615741.250.51
BFC-15010 THRU 15080115030x48615741.50.751.25
BFC-20010 THRU 20080222030x728181420.751.5
BFC-25010 THRU 25080225030x849393420.751.5
BFC-30010 THRU 30080231536x728181420.751.5
BFC-40010 THRU 40080239036x849393420.751.5
BFC-50010 THRU 50080250042x849393420.751.5
BFC-75010 THRU 75080275048x9610510562.512
BFC-100010 THRU 1000802100048x12012912962.512

Variable Table

Tank Dia.FigurePumpBDEF
181CC29242629
181CG35272831
181CK41303336
181CKH41303336
241CC29273236
241CG35303438
241CK41333943
241CKH47363943
301CC29303842
301CG35334044
301CK47394549
301CKH47394549
302CC31315155
302CG31315155
302CK31315155
302CKH31315155
362CC37375761
362CG37375761
362CK37375761
362CKH37375761
422CC43436367
422CG43436367
422CK43436367
422CKH43436367
482CC49496973
482CG49496973
482CK49496973
482CKH49496973
cad - bfu-bfc-specifications_46a.gif

Engineering Equivalents Table

1,000 sq. ft. E.D.R.=240,000 BTU per hr.
1,000 sq. ft. E.D.R.=247 lbs. Water Evap. per hr.
1,000 sq. ft. E.D.R.=1/2 gal. Water Evap. per min.
1 sq. ft. E.D.R.=240 BTU per hr. (Steam)
1 sq. ft. E.D.R.=150 BTU per hr. (Hot Water)
1 sq. ft. E.D.R.=1/4 lb. Water Evap. per hr.
1 Boiler HP.=33,475 BTU per hr.
1 Boiler HP.=34.5 lbs. Water Evap. Per hr. (at 212 degrees F)
1 Boiler HP.=.07 gal. Water Evap. per min.
1 Boiler HP.=140 sq. ft. E.D.R. (Steam)
1 Boiler HP.=222 sq. ft. E.D.R. (Hot Water)
1 lb. P.S.I.=2.31 ft. of Water
1 lb. P.S.I.=2.04 ins. of Mercury
1 lb. P.S.I.=.068 Atmosphere
1 ft. of Water=.433 lbs. P.S.I.
1 ft. of Water=.882 ins. of Mercury
1 ft. of Water=.029 Atmosphere

SIZING DATA

PUMP CAPACITY: Multiply the developed boiler H.P. by .07 to determine the evaporation rate of the boiler (expressed in gallons per minute). Next, multiply this evaporation rate by 3 to determine the capacity of the feed pump (in G.P.M). This factor of 3 allows the pump to cycle at reasonable intervals. If one boiler is being fed, a simplex unit may be used, but a duplex unit (with each pump sized to independently feed the boiler) has the advantage of providing an emergency standby pump or alternating the pumps for even wear. If two boilers are being fed, use duplex unit and size one pump for each boiler (specify 4-pole double throw transfer switch to cross pump-boiler assignment) or use triplex unit with each pump sized to feed one of the boilers (specify transfer switch to use one pump for standby service).
PUMP DISCHARGE PRESSURE:
Discharge pressures in the Engineering Selection Table are pressures at the pump. To compute, add boiler working pressure plus static head (from pump center line to boiler connection center line) plus discharge line friction loss (including pipe, fittings, valves, etc.). Convert all factors to P.S.I. before adding. Static head plus friction loss plus a small residual pressure can be estimated at 5 P.S.I. in most cases.
RECEIVER SIZE:
Allow approximately one gallon of receiver capacity for each H.P. of boiler(s) being served. (Example: If two (2) 250 H.P. boilers are being fed by a duplex unit, receiver should have 500 gallon capacity.

cad - bfu-bfc-engineering_43a.gif


Selection Table

Unit No.Boiler H.P.Pump Disch. Press P.S.I.G.Boiler Evap. G.P.M.Pump Capacity G.P.MMotor H.P. 1750 RPMMotor H.P. 3450 RPMReceiving Tank Capacity Gal.Pump Disch. Size Type 1750 RPMPump Disch. Size Type 3450 RPM
BFC-151015101.0430.250.33261-1/4CC1-1/4CC
BFC-151515151.0430.330.33261CG1-1/4CC
BFC-152015201.0430.50.33261CG1-1/4CC
BFC-153015301.04310.75261-1/2CK1-1/4CC
BFC-154015401.04321261-1/2CK1-1/4CC
BFC-155015501.04331.5262CKH1-1/4CC
BFC-156015601.04352262CKH1CG
BFC-157015701.0437.53262CKH1CG
BFC-158015801.043-326-1CG
BFC-301030102.0760.250.33331-1/4CC1-1/4CC
BFC-301530152.0760.330.33331CG1-1/4CC
BFC-302030202.0760.50.33331CG1-1/4CC
BFC-303030302.07610.75331-1/2CK1-1/4CC
BFC-304030402.07621331-1/2CK1-1/4CC
BFC-305030502.07631.5332CKH1-1/4CC
BFC-306030602.07652332CKH1CG
BFC-307030702.0767.53332CKH1CG
BFC-308030802.076-333-1CG
BFC-501050103.45100.250.33451-1/4CC1-1/4CC
BFC-501550153.45100.330.33451CG1-1/4CC
BFC-502050203.45100.50.33451CG1-1/4CC
BFC-503050303.451010.75451-1/2CK1-1/4CC
BFC-504050403.451021451-1/2CK1-1/4CC
BFC-505050503.451031.5452CKH1-1/4CC
BFC-506050603.451052452CKH1CG
BFC-507050703.45107.53452CKH1CG
BFC-508050803.4510-345-1CG
BFC-751075105.18150.250.331001-1/4CC1-1/4CC
BFC-751575155.18150.50.331001CG1-1/4CC
BFC-752075205.18150.750.331001CG1-1/4CC
BFC-753075305.181510.751001-1/2CK1-1/4CC
BFC-754075405.1815211001-1/2CK1-1/4CC
BFC-755075505.181531.51002CKH1-1/4CC
BFC-756075605.1815521002CKH1CG
BFC-757075705.18157.531002CKH1CG
BFC-758075805.1815-3100-1CG
BFC-10010100106.9200.250.331001-1/4CC1-1/4CC
BFC-10015100156.9200.50.331001CG1-1/4CC
BFC-10020100206.9200.750.331001CG1-1/4CC
BFC-10030100306.9201.50.751001-1/2CK1-1/4CC
BFC-10040100406.920211001-1/2CK1-1/4CC
BFC-10050100506.92031.51002CKH1-1/4CC
BFC-10060100606.920531002CKH1CG
BFC-10070100706.9207.531002CKH1CG
BFC-10080100806.920-3100-1CG
BFC-150101501010.4300.50.331501CG1-1/4CC
BFC-150151501510.4300.750.51501CG1-1/4CC
BFC-150201502010.4300.750.51501CG1-1/4CC
BFC-150301503010.4301.50.751501-1/2CK1-1/4CC
BFC-150401504010.430311501-1/2CK1-1/4CC
BFC-150501505010.430321502CKH1-1/4CC
BFC-150601506010.430531502CKH1CG
BFC-150701507010.4307.531502CKH1CG
BFC-150801508010.430-5150-1CG
BFC-200102001013.8400.330.52201-1/4CG1-1/4CC
BFC-200152001513.8400.750.752201-1/2CG1-1/4CC
BFC-200202002013.84010.752201-1/2CG1-1/4CC
BFC-200302003013.840212201-1/2CK1-1/4CC
BFC-200402004013.84031.52201-1/2CK1-1/4CC
BFC-200502005013.840332202CKH1-1/4CC
BFC-200602006013.840532202CKH1CG
BFC-200702007013.8407.552202CKH1CG
BFC-200802008013.840-5220-1CG
BFC-250102501017.3500.50.752501-1/4CG1-1/4CC
BFC-250152501517.3500.750.752501-1/2CG1-1/4CC
BFC-250202502017.3501.50.752501-1/2CG1-1/4CC
BFC-250302503017.350212501-1/2CK1-1/4CC
BFC-250402504017.350322501-1/2CK1-1/4CC
BFC-250502505017.350532502CKH1-1/4CC
BFC-250602506017.350552502CKH1CG
BFC-250702507017.3507.552502CKH1CG
BFC-250802508017.350-5250-1CG
BFC-300103001020.7600.750.753151-1/2CG1-1/2CC
BFC-300153001520.760113151-1/2CG1-1/2CC
BFC-300203002020.7601.51.53151-1/2CG1-1/2CC
BFC-300303003020.760223151-1/2CK1-1/2CC
BFC-300403004020.760333151-1/2CK1-1/2CC
BFC-300503005020.760553152CKH1-1/2CC
BFC-300603006020.760553152CKH1CG
BFC-300703007020.7607.553152CKH1CG
BFC-300803008020.760-7.5315-1-1/2Cg
BFC-400104001027.68010.753901-1/2CG1-1/2CC
BFC-400154001527.6801.513901-1/2CG1-1/2CC
BFC-400204002027.68021.53902CG1-1/2CC
BFC-400304003027.680323901-1/2CK1-1/2CC
BFC-400404004027.680533902CK1-1/2CC
BFC-400504005027.680553902CKH1-1/2CG
BFC-400604006027.6807.57.53902CKH1-1/2CG
BFC-400704007027.6807.57.53902CKH1-1/2CG
BFC-400804008027.680-10390-1-1/2CG
BFC-500105001034.5100115002CG1-1/2CC
BFC-500155001534.51001.515002CG1-1/2CC
BFC-500205002034.510021.55002CG1-1/2CC
BFC-500305003034.5100335001-1/2CK1-1/2CC
BFC-500405004034.5100555002CK1-1/2CC
BFC-500505005034.5100555002CKH1-1/2CG
BFC-500605006034.51007.57.55002CKH1-1/2CG
BFC-500705007034.5100107.55002CKH1-1/2CG
BFC-500805008034.5100-10500-1-1/2CG
BFC-750107501051.81501.537502CG2-1/2CG
BFC-750157501551.8150237502CG2-1/2CG
BFC-750207502051.8150337502-1/2CG2CG
BFC-750307503051.8150557502CK2CG
BFC-750407504051.81507.57.57502-1/2CK2CG
BFC-750507505051.81507.57.57502CKH2CG
BFC-750607506051.815010107502CKH2CG
BFC-750707507051.815015157502CKH2CG
BFC-750807508051.8150-15750-2CG
BFC-100010100010692002310002-1/2CG2-1/2CG
BFC-100015100015692003310002-1/2CG2-1/2CG
BFC-100020100020692005310002-1/2CK2-1/2CG
BFC-100030100030692005510002-1/2CK2CG
BFC-100040100040692007.57.510002-1/2CK2CG
BFC-10005010005069200101010002CKH2CG
BFC-10006010006069200151010002CKH2CG
BFC-10007010007069200151510002CKH2CG
BFC-10008010008069200-151000-2CG
Units operating at 1750 R.P.M., add -4 to unit number (Example: BFC-15020-4); units operating at 3450 R.P.M., add -2 to unit number (Example: BFC-15020-2).
Units are available for discharge pressures higher than 80 psig, to a maximum of 125 psig.


SUGGESTED SPECIFICATIONS FOR ARCHITECTS AND ENGINEERS:

Furnish and install where indicated on plans, a Type BFC Simplex (or Duplex; Triplex; Quadruplex) Boiler Feed Unit, as manufactured by Federal Pump Corp., Unit No. BFC- ____ sized to provide feed water to _____boiler(s), (each) developing _____boiler H.P. (Each) pump shall deliver ____ G.P.M. at a discharge pressure of ____ PSIG at the pump(s).

Unit shall be factory assembled by the pump manufacturer, including receiver and accessories plus pump(s) and motor(s) all mounted on a single steel base with pump suction complete piping.Pump(s) shall be close-coupled, end-suction, bronze-fitted, centrifugal type with balanced and enclosed impeller, leakless mechanical shaft seal and bronze shaft sleeve; driven by____H.P., ____ phase, ____ cycles, ____ volts, ____ R.P.M. ball bearing, drip-proof (or totally enclosed; explosion-proof) motor(s).

Single phase motors in fractional H.P. frame sizes shall have built-in thermal overload protection. Single phase motors in integral H.P. frame sizes and all three phase motors shall be provided with across-the-line type manual-reset magnetic starters in NEMA 1 general purpose (or NEMA 4 Water-tight; NEMA 7 Explosion-proof) wall-mounting enclosure(s).

Receiver shall be of heavy steel construction, with anti-corrosion interior coating, gauge glass, thermometer, and connections for return, vent and drain. Makeup water valve, flange-mounted on tank head, shall be of all-bronze construction, float operated with makeup water strainer. Receiving tank capacity shall be _____gallons.

Furnish and install on (each) boiler a boiler water level controller to automatically operate the pump(s), with low-water cut-off and alarm switch, plus alarm bell. Controller shall be equal to McDonnell-Miller No. 150 (for boiler pressures up to 150 P.S.I.) or No. 94 (for boiler pressures up to 250 P.S.I.). (Controllers not usually furnished by Federal).

SUGGESTED SPECIFICATIONS FOR ARCHITECTS AND ENGINEERS:

TYPE BFC

BOILER FEED UNIT

DUPLEX

(ONE BOILER/TWO PUMP OPERATION)

DATA NO. 127.1

Furnish and install as shown on-plans, a Federal Pump Corporation type BFC duplex boiler feed unit sized to provide feed water to one boiler. Each pump shall be sized as shown in the pump schedule.

The unit shall be factory assembled by the pump manufacturer, including the feed water receiver, pump and motor units, and accessories mounted on a steel base with pump suction piping complete.

Pumps shall be close-coupled, end suction, bronze-fitted centrifugal type, with centerline discharge for automatic venting. Back pullout design shall permit removal of the motor and rotating assembly without disturbing piping.

Each pump shall have an enclosed balanced bronze impeller, mechanical shaft seal and copper by-pass from the pump discharge into the seal chamber. Pumps shall be close-coupled to standard NEMA JM-frame motors in open, drip-proof enclosures, rated as shown in the pump schedule.

Furnish a magnetic starter for each motor with overload protection on each phase and a hand-off-automatic selector switch. Furnish a transfer switch to permit manual selection of the lead pump. Starters and transfer switch shall be factory mounted on the unit and wired to the motors.

The pumps shall be controlled by a boiler water level controller mounted on the boiler, as herein specified. The feed water receiver shall be of heavy steel construction with convex heads, gauge glass, thermometer, and connections for return, vent and drain. A makeup water valve, flange mounted on the tank head, shall be all-bronze, float operated type with strainer. The receiver capacity shall be as shown in the pump schedule.

Pump Schedule:

No. of Boilers: 1 No. of Pumps: 2

Unit Model Number: BFC-

Pumps:_______GPM per pump_______ PSI discharge pressure

Motors:_______HP ________ RPM _______Phase, 60 cycles, ______ volts

Receiver: _______ gallon capacity

Project:

 

 

SUGGESTED SPECIFICATIONS FOR ARCHITECTS AND ENGINEERS:

Type BFC

Boiler Feed Unit

Triplex

(Two Boiler/Three Pump Operation)

DATA NO. 127.2

Furnish and install as shown on plans, a Federal Pump Corporation type BFC triplex boiler feed unit sized to provide feed water to two boilers. Each pump shall be sized as shown in the pump schedule.

The unit shall be factory assembled by the pump manufacturer, including the feed water receiver, pump and motor units, and accessories mounted on a steel base with pump suction piping complete. Pumps shall be close-coupled, end suction, bronze-fitted centrifugal type, with centerline discharge for automatic venting. Back pullout design shall permit removal of the motor and rotating assembly without disturbing piping.

Each pump shall have an enclosed balanced bronze impeller, mechanical shaft seal and copper by-pass from the pump discharge into the seal chamber. Pumps shall be close-coupled to standard NEMA JM-frame motors in open, drip-proof enclosures, rated as shown in the pump schedule. Furnish a magnetic starter for each motor with overload protection on each phase and a hand-off-automatic selector switch.

Pump no. 1 shall feed boiler no. 1 and pump no. 2 shall feed boiler no. 2. A manual transfer switch shall permit pump no. 3 to act as standby for either pump no. 1 or pump no. 2. Starters and transfer switch shall be factory mounted on the unit and wired to the motors. The pumps shall be controlled by a boiler level controller mounted on each boiler, as herein specified.

The feed water receiver shall be of heavy steel construction with convex heads, gauge glass, thermometer, and connections for return, vent and drain. A makeup water valve, flange mounted on the tank head, shall be all-bronze, float operated type with strainer. The receiver capacity shall be as shown in the pump schedule.

Pump Schedule:

No. of Boilers: 2 No. of Pumps: 3

Unit Model Number: BFC-

Pumps:_______GPM per pump_______ PSI discharge pressure

Motors:_______HP ________ RPM _______Phase, 60 cycles, ______ volts

Receiver: _______ gallon capacity

Project: _______________________________________________