RECEIVER: Heavy welded steel construction, designed for vented operation.
PUMP: Bronze fitted, close-coupled, centrifugal design, with bronze sleeve fully protecting the shaft. Mechanical shaft seals are standard. Maximum water temperature at pump suction is 210°F.
MOTOR: Drip-proof, ball bearing design. Units are avaiable with 1750 RPM or 3450 RPM motors.
FLOAT SWITCH: One for each pump, provides automatic operation; mounted and wired on unit.
STARTER: All polyphase units (208v. or 230/460v.), and integral H.P. single phase units (115/230v.) are furnished with magnetic starters mounted and wired on the unit. Single phase fractional H.P. motors have built-in overload protection and do not require magnetic starters.